Wet Vent
Definitions:
Wet vent means a waste
pipe that also serves as
a vent pipe.
There are two types of fixtures in
a wet vent installation:
wet venting fixture and wet
vented fixture.
7.5.7.1.(1) :
there may be up to
three fixtures installed in a wet vent group:
- one fixture is
wet venting,
- one or two fixtures
are wet
venting.
7.5.7.1.(1)(b):
|
Only the wet vented fixture
is a water closet
or other fixture using a siphonic trap
|
Installation
Requirements:
- All the fixtures must be
located at the same
floor.
- Wet vent
must connect to the horizontal waste
pipe of P-trapped
wet vented fixture
|
Wet vent cannot connect to
the vertical waste pipe of a P-trapped
fixture
|
- 7.5.7.1.(1)
(c):
wet
vent must be installed 450
mm minimum or 1500 mm maximum downstream from
weir
of a P-trapped wet vented fixture.
- 7.5.5.2.(3):
|
Wet vent is not required to
be connected above the horizontal
center line of the soil or
waste pipe
|
- wet vent
may connect to either vertical or
horizontal waste pipe of a wet
vented siphonic
trap.
|
There are no limits placed on
how close a
wet vent may connect to a siphonic fixture
|
however
|
Wet vent must be located
within 1500 mm of the elbow serving a water
closet or any floor mounted siphonic
fixture
|
- 7.5.7.1.(1)(d):
At least one of
the wet venting
fixtures must be drained through
a continuous waste and
vent
-
-
If two wet
venting fixtures connect to
the wet vent
at the same level, the wet
venting fixtures must
be dual vented.
-
If two wet
venting fixtures connect to
the wet vent
not at
the same level, they must be
separately vented with one of the fixtures drained
through a continuous waste and vent.
-
|
|
There are no limits
placed on the developed length of a wet
vent
|
|
Sizing Wet
Vent:
7.5.7.1.(1)(d):
The minimum size of
a wet vent is determined by the size of the
wet venting fixture trap
|
Trap, in
|
min Wet Vent, in
|
|
1 1/4, 1 1/2
|
1 1/4
|
|
2
|
1 1/2
|
|
3, 4, 6
|
2
|
The vertical
extensions of a wet vents above the wet venting fixture
connection is sized as a branch vent according to
Table 7.5.7.2.A..
|