Water Distribution System
1.1.3.2.
Water distribution system means an assembly
of pipes, fittings, valves and appurtenances that conveys water
from the water service pipe or private water supply system to
water supply outlets, fixtures, plumbing appliances and
devices.
1.1.3.2.
Water service pipe means a pipe on the
property that conveys potable water from a water works or private
water source to the inside of the building.

Water distribution systems must connect to
one of two different water supply locations. These are either a
public water main or if a main is not available, to private
potable water system.
7.1.6.3.
-
Except as provided in Sentence (2), every
water distribution system shall be connected to a public water
main or if no public water main is available to a potable
private water supply system.
-
Where a supply of potable water is
unavailable or insufficient to supply water to a plumbing
system, non-potable water may be used for flushing of water
closets, urinals or the priming of traps, and the piping
conveying the non-potable water shall be installed in
conformance with Section 7.7.
There must be no interconnection between the
potable and non-potable water systems.
7.7.1.1.(1)
A non-potable water piping shall not be
connected to a potable water system.
7.7.3.1.(1)
Non-potable water piping shall not be
located
7.7.3.2.(1)
An outlet from a non-potable water system
shall not be located where it can discharge into
-
a sink or lavatory,
-
a fixture into which an outlet from a
potable water system is discharged,
-
a fixture that is used for a purpose
related to the preparation, handling or dispersing of food,
drink or products that are intended for human
consumption.
7.7.2.1.(1)
Non-potable water piping shall be identified
by markings that are permanent, distinct and easily
recognized.
|
7.6.1.1.
-
Potable water systems must be
designed, fabricated and installed in accordance with
good engineering practice.
-
Every fixture supplied with
separate hot and cold water controls shall have the
hot water control on the left and cold on the
right.
-
Where hot and cold water are
mixed and the temperature is regulated by a single,
unmarked, manual control, a movement to the left
shall increase the temperature and a movement to the
right shall decrease the temperature.
|

|
7.6.1.2.(1)
A water distribution system shall be
installed so that the system can be drained or blown out with air
and outlets for this purpose shall be provided.
In normal circumstances, the distribution
system will drained down through the lowest faucets on the
system, as in the laundry tub faucet.
7.6.2.2.(1)
Every newly installed part of a potable water
system shall be cleaned and free of any matter that may affect
the health of a person before being put into service (See
Appendix A.) (with chemicals)
The minimum diameter of a water distribution
system is 3/4" from the connection of the water service pipe to
the branch that supplies the hot water tank.
7.6.3.2.(2)
No water system between the point of
connection with the water service pipe or the water meter and the
first branch that supplies a water heater, shall be less than
3/4" size.
The minimum water service size is
3/4".
7.6.3.4.(1)
Every water service pipe shall be not less
than 3/4" trade size.

The minimum water pipe size that may be
installed to serve a number of common fixtures is listed
in Table 7.6.3.1.. Most of the common fixtures listed in the table require
a 1/2" supply with a few having a minimum of 3/8" and one
fixture, a direct flush valve water closet requiring a minimum
pipe size of 1".
7.6.3.1.(1)
Except as provided in Sentence (2), the size
of every water distribution system that supplies water to a
fixture or device shall comply with Table 7.6.3.1..
We are permitted to use the supply tube
instead of prescribed pipes as long as the length of 3/8" tube is
not more than 14"
|
7.6.3.1.(2)
Where a pipe in a water
distribution system is not directly connected to a
fixture or a fixture faucet but is connected with a
flexible tube of a diameter smaller than that specified
by Table
7.6.3.1., the developed
length of the connector shall not be more than 355 mm
(14"0 and, where 3/8" pipe of iron pipe size is used,
the maximum length shall not exceed 914 mm (3').
|

|
7.6.3.3.(1)
Where the static water pressure exceeds 550
kPa (79.8 psi), a pressure reducing valve shall be installed to
limit the maximum static pressure to not more than 550 kPa (79.8
psi) in areas that may be occupied.
7.2.10.12.(1)
Direct acting water pressure reducing valves
for domestic water supply systems shall conform to CSA-B356,
Water Reducing Valves for Domestic Water Supply Systems".
7.2.1.3.(2)
Materials and equipment that have been used
for a purpose other than the distribution of potable water shall
not be subsequently used in a potable water system.
7.6.2.1.
- Connections to potable water systems shall be designed and installed so that non-potable system water or substances that may render the non-potable cannot enter the system.
- No connection shall be made between a potable water system supplied with water from a drinking-water system and any other potable water system without the consent of the water purveyor.
7.6.2.3. Back Siphonage
- Every potable water system that supplies a fixture or tank that is not subject to pressure above atmospheric shall be protected against back-siphonage by a backflow preventer.
- Where a potable water supply is connected to a boiler, tank, cooling jacket, lawn sprinkler system or other device where a non-potable fluid may be under pressure that is above atmospheric or the water outlet may be submerged in the non-potable fluid, the water supply shall be protected against backflow by a backflow preventer.
- Where a hose bibb is installed outside a building, inside a garage, or where there is an identifiable risk of contamination, the potable water system shall be protected against backflow by a backflow preventer.
- Where a potable water system system serves a fire protection system, the fire protection system shall be isolated from potable water system in the following manner:
- a wet sprinkler fire protection system containing water only shall be provided with a listed alarm check valve installed in conformance with NFPA 13, "Installation of Sprinkler Systems".
- a wet standpipe fire protection containing water only shall be provided with a resilient seated check valve.
- a wet sprinkler or wet stand pipe fire protection system containing anti-freeze or chemicals shall be provided with a reduced pressure principle backflow preventer certified to CAN/CSA-B64.4 Series, "Backflow Preventers, Reduced Pressure Principle Type (RP)".
- a dry sprinkler or dry stand pipe fire protection system does not require isolation.
- a water storage tank fire protection system shall be provided with a backflow preventer certified to CAN/CSA-B64.4 Series, "Backflow Preventers and Vacuum Breakers".
- A fire hydrant fire protection fire protection system does not require isolation.
- a fire service main shall be provided with a reduced pressure principle backflow preventer certified to CAN/CSA-B64.4, "Backflow Preventers, Reduced Pressure Principle Type (RP)" if it is connected to more than one of the following different sources of supply:
i) a drinking water system, or
ii) a source of non-potable water.
- Backflow prevention devices shall be provided in conformance with Sentence 7.2.10.10(1).-link neitralizing_dilution_tanks
- Building of residential occupancy within the scope of Part 9 are not require to be isolated unless they have access to an auxiliary water supply.
|