Vent Stack

Purpose:

to maintain atmospheric pressure throughout the length of the soil and waste stacks, provide a convenient connection point for individual, branch and stack vents.


Definition:

"Vent Stack means a vent pipe that is connected at its upper end to a header or is terminated in an open air and that is used to limit pressure differential in a soil or waste stack."


Installation:

7.5.3.2.(1)

Vent Stack must be installed in conjunction with the soil or waste stack

  • in any building of 2 or more storeys except residential ,
  • in residential buildings of 4 storeys and more,
    where back vents, relief vents or circuit vents (vent piping in general) are installed.

7.5.3.2.(2)

A vent stack is not required to be installed in conjunction with the soil or waste stack in a residential building of 3 storeys or less.


Connection (lower end):

  • in residential buildings of 4 and more storeys, other buildings of 2 and more storeys:

7.5.3.2.(3)(a)(i) "...at or below the lowest horizontal sanitary drainage pipe connected to the waste or soil stack":


vs3  vs4  vs5


7.5.3.2.(3)(a)(ii) "...to the building drain immediately downstream of the stack connection":



  • in residential buildings of 3 and less storeys:
    fixtures individual vents can be the beginning of the vent stack


vs7

see also Code: A-1.1.3.2.

On this pictures Vent Stack is not installed in conjunction with the soil or waste stack see why.


Connection ( vent pipes to the vent stack ):

  • 7.5.5.4. (1)

"The upper end of every vent pipe shall be above the flood level rim of the highest fixture it serves before connecting to another vent pipe."

  • 7.5.5.4. (2)

"No vent pipe shall be so arranged that it will serve as a bypass in the event of an obstruction in the drainage pipe."


vs8


Sizing

  • diameter
    As a rule size of the Vent Stack is half the size of the soil or waste stack at the lowest point of connection
    Table 7.4.10.5.B.
  • length
    Table 7.4.10.5.B.


Usually the reason to increase the diameter of a vent stack is the connection of branch vents, stack vents and individual vents, not the overall developed length.


7.5.7.2. Branch Vent Sizing

  1. No branch vent and its connecting branch shall be smaller in diameter than the diameter calculated in accordance with Table 7.5.7.2.A and where Table 7.4.10.5.B. is not applicable to the vent, the maximum length of the vent shall be calculated in accordance with Table 7.5.7.2.B.
  2. For the purpose of Table 7.4.10.5.B. and Table 7.5.7.2.B., the length of a vent stack or vent shall be its developed length of vent piping from the vent stack or stack vent where the header terminates to the most distant vent or stack connected to it.

7.5.7.3.(1) Developed Length

For the purpose of Table 7.4.10.5.B and Table 7.5.7.2.B, the length of a vent stack or stack vent shall be its developed length from its lower end where it connects to the drainage piping to its upper end where it connects to a header or goes directly to open air.


A vent stack shall at each point of interconnection with a branch vent be not smaller than the minimum size permitted by Table 7.5.7.2. A..


vs9


Fixtures can be connected to a vent stack:

if

  • total hydraulic does not exceed 8 fixture units,
  • at least 1 fixture is connected to the vertical portion of the vent stack and upstream of any other fixture,
  • no other fixtures is connected downstream of a water closet,
  • all fixtures are located at the lowest storey served by the vent stack.

vs10
Visualization of how it might be if to connect modified stack venting to the vent stack:


vs11

Aditional Requirements


Termination ( connection of the upper end):

7.5.5.5.(1)

The upper end of every vent pipe that is not terminated in open air shall be connected to a venting system that is terminated in open air:












































































































pr100


Terminating independently in open air

vs12

Terminating into a Stack Vent
vs13
Terminating into header

vs14

see also location of vent pipe terminals