|
Stack Vent
Definitions
Stack vent is an arrangement of group venting when fixture
traps are vented through the soil stack which terminates
into a header or open air and no additional venting is
required.
For a better explanation go
to 1.1.3.2.(1)
Installation Requirements
(7.5.2.1.)
- The stack must be a soil
stack of minimum 3" size that extends as a
stack vent
that means no discharge from any other fixture located on
any other higher storey.
- All stack vented fixtures
must be located at the same floor.
- The maximum number
of stack vented fixtures
is 6.
The
lowest fixture in a stack vented group is a water closet.
The
maximum number of water closets
in a stack vented group is
2.
The
maximum number of other fixtures connected above the water closet
is 4.
- Where
two water
closets installed, they must be connected
at the same level
to the stack.
All other fixtures
must be connected directly and
independently to the
stack above the center line of
water closets and the
uppermost fixture must be connected to the vertical portion of the
stack.
-
Where there is only one water closet
in a stack vented group, it may connect to the
vertical stack or horizontal
continuation of the stack and
remaining fixtures upstream of the water closet must be
connected directly and
independently to the stack and
the uppermost fixture
must be connected to the
vertical portion of the stack.
- The total number
of fixture units
connected above the water closet
is 8.
- Maximum size of a
fixture drain connected above the water closet is
2".
- No siphonic trap
connected above the water closet is permitted.
Additional Requirements
- The developed length of a
fixture drain measured from the trap weir to the stack is 2
pipe diameters minimum or 1500 mm maximum.
- maximum
fall is
1 fixture drain
pipe diameter
- maximum
change of direction
is
-
1350 for a
P-trap,
-
2250 for a S-trap.
- No other drainage pipe
may connect to fixture drain between the fixture trap and
its protective vent.
- The fittings used to
connect the two water closets to the soil stack may
be
- Double
Combination Y and 1/8 Bend or Double Long Turn
TY
- Double Y
& two 450
elbows
consult Table 7.2.4.5.
- Requirements that
fixtures must be connected "above the center line of the
water closet" permit the installation of a
combination drainage
fitting:
Only bear in mind
that this fitting is not mentioned
in the Ontario Code
and Guide for Plumbing
- If there is a need to
connect an additional fixture to the stack where a stack
vent is installed, the fixture drain must connect
below the
water closet of the stack vented group and the fixture trap
vent can connect back into the stack above the flood level
rim of the highest fixture, or terminate into header
or in open air.
7.5.3.1.(1)
The upper end of every soil or waste stack shall terminate in a stack vent and the stack vent shall terminate in open air outside the building or connect directly or through a header to another stack vent, a vent stack that does terminate in open air outside the building.
-
at the same floor
-
at the floor as a result of
alteration
|