Sewage Tanks, Storm Water Sumps, Sewage and Sump PumpsThe vast majority of both sumps and sewage pumps are of the centrifugal kind.
Sump and Sewage Pumps (Ejectors) There are generally two types of basement water pumps: pedestal and submersible. The pedestal pump's motor is mounted above the pit, where it is more easily serviced but also more conspicuous. The submersible pump is entirely mounted inside the pit, and is specially sealed to prevent electrical short circuits. Although the submersible models are known for quieter operation, they are considerably more expensive. Although there is no considerable difference in performance, and both styles are considered fine for basement water drainage purposes.
Grinder Pump
Effluent Pump
Pump Controls
Sumps or Tanks
7.4.8.3.
Note: The diameter of the discharge pipe from a sewage or storm pump is determined by the manufacturer.
The discharge piping from a sewage pipe is referred to as a "force main" and is defined this way: "Force main means a sanitary drainage pipe through which sanitary sewage is conveyed by mechanical or pneumatic propulsion".
Venting Sewage Tanks 7.5.4.1.(1) Every tank that receives sanitary sewage shall be provided with a vent pipe that is connected to the top of the tank and that is sized in accordance with Article 7.5.6.5..
7.5.6.5.
i) 1 /1/4" and ii) one trade size smaller than the inlet pipe.
Fixture Connection Fixtures discharging to a sewage tank and pump must be trapped and vented just like any other fixture installed in the sanitary drainage system. Circuit Vented branch must not connect to a sewage tank installation (7.5.5.2.(1)).
Determining the Diameter of a building Drain The total GPM load of the sewage pump at the point of connection to the sanitary building drain should be added to the GPM load of the sanitary building drain. This is the only occasion when doing pipe sizing that gallons per minute flows are added together in order to determine the diameter of a drainage pipe.
7.4.10.4(1) For the purpose of determining the size of sanitary drainage pipe in accordance with Table 7.4.10.3.C. pumped discharge and other continuous and semi-continuous flows shall be calculated in gallons per minute flow and added to the drainage rate in gallons per minute flow from Table 7.4.10.3.B.
Example The sanitary building drain carries 170 f. u. or 67 GPM. The diameter of the sanitary building drain is 4". The rating of the sewage pump is 30 GPM. Therefore, at the point of connection, the total combined load on the building drain is 97 GPM. Table 7.4.10.3.C says that 4" pipe with a slope 1:50 can carry up to 91 GPM. That is why at the point of the connection the drain must be increase to 5" to accommodate the 97 GPM.
|