Plumbing Fixtures
Definition:
Plumbing fixture means a receptacle, plumbing
appliance, apparatus or other device that discharges sewage or clear ware
waste and includes a floor drain.
7.1.5.1.(1)
Plumbing facilities shall be provided in accordance
with Subsection 3.7.4. and Section 9.31 of this code.
The only plumbing fixtures we are required to install
under Part 7 are floor drains found in Code section
7.1.5.2. and
interceptors found in Code section 7.4.4.3..
7.1.7.1.(1)
Plumbing fixtures shall not be installed in a room
that is not lighted and ventilated in accordance with the appropriate
requirements of Part 3 and 9.
7.1.7.2.(1)
Every fixture, plumbing appliance, interceptor,
cleanout, valve, device or piece of equipment shall be so located that it
is readily accessible for use, cleaning and maintenance.
7.2.1.3.(1)
Used materials and equipment, including fixtures,
shall not be reused unless they meet the requirements for this Part for
new materials and equipment and are otherwise
satisfactory for their intended use.
Plumbing fixtures that are intended to be installed
must be accredited by the Standards Council of Canada:
7.2.1.4.(2)
Where a component of a plumbing system is required by
this Code to comply with a standard and the compliance is not certified
by a testing agency accredited by the Standards Council of Canada for the
testing of the component in question and, where an inspector requests
proof of compliance, proof of compliance shall be produces by the person
proposing to install or have installed the components, and without such
proof the component shall not be installed as a permanent part of any
plumbing system.
7.2.1.4.(3)
The lack of certification markings on a product or
plumbing component shall be regarded as proof, in the absence of evidence
to the contrary that no certification exists.
7.2.1.4.(4)
If a component of a plumbing system is required to be
certified to a standard, the certification shall be made by a testing
agency accredited for that purpose by the Standard Council of
Canada.
Currently the only fixtures which must be CSA
approved are water closets
and urinals.
7.6.4.2.(1)
Water closets and urinals shall be certified to
CAN/CSA-B45.0 ...
7.2.2.1.(1)
Except for the area designed to be slip proof in such
fixtures, every exposed area of a fixture shall have a smooth, hard
corrosion resistant surface that is free from flaws and blemishes that
may interfere with cleaning.
|

Vitreous China
|

Enameled Cast Iron
|

Stainless Steel
|

Fiberglass
|
|

Plastics
|

Acrylic
|

Terrazzo
|
|
In the normal way of things all plumbing fixtures
should connect to the sanitary drainage system. However there are
exceptions.
Water
Closets
|

|
Every water closet installed must have a seal installed between
the bowl and the flange in order to create a tight seal. The
type of material used to make the water closet seal is listed
in code section
7.3.3.9.(4)
Every floor flange shall be set on a firm base and bolted to
the trap flange of the fixture, and every joint shall be sealed
with a natural rubber, synthetic rubber or asbestos graphite
gasket, or with a closet setting compound.
7.2.10.2.(1)
Every screw, bolt, nut and washer shall be of brass or equally
corrosion resistant material when used
- to connect a water closet to a water close
flange,
- to anchor the water closet flange to the floor,
- to anchor the water closet to the floor
|
Types of Water Closets
|

Siphon Jet
|

Blow-out
|
|
7.3.3.9.(1)
Every pedestal urinal, floor-mounted water closet or
S-trap standard shall be connected to a fixture drain by a floor flange,
except that a cast-iron trap standard may be caulked to a cast-iron
pipe.
|

Fixture carrier for a wall mounted water closet provides
connection into DWV system and also support for the fixture off
the floor.
|
|
7.3.4.1.(2)
every floor or wall mounted water closet
bowl shall be securely attached to the floor or wall by means
of a flange and shall be stable.
7.3.3.9.
-
Except as provided in Sentence (3), every
floor flange shall be of brass.
-
Where cast iron or plastic pipe is used,
a floor flange of the same material may be used.
-
Where a lead water closet stub is used,
the length if the stub below the floor flange shall be at
least 75 mm.
7.4.2.2.(3) No
other fixture shall be connected to a lead bend or stub that
serves a water closet.
|
7.1.7.2.(2)
Except for Eastern-Style toilets, where a water
closet is installed in a washroom for public use it shall be of the
elongated type and provided with a seat of the open front
type.
Table 7.6.3.1.
minimum water supply pipe size for a flush tank water
closet is 1/2",
minimum water supply pipe size for a direct flush
valve is 1".
Where a water closet is connected to a water
distribution system by use of 3/8" flexible tubing, the maximum length of the tubing
should be 355 mm.
7.4.9.2.
-
The size of every drainage pipe that serves a water
closet shall be at least 3".
-
The size of every horizontal branch downstream of
the third water closet fixture drain connection shall be at least
4".
-
The size of every soil stack that serves more than
6 water closets shall be at least 4".
Urinals
|

Stall Urinal
|

Wall Hung,
Integral Trap Urinal
|

7.2.2.6.(1)
No trough urinal shall be used as part of a plumbing system.
|
|
The minimum water pipe size to supply a urinal
equipped with a flush tank is 1/2", a direct flush valve or flushometer
is 3/4", and a self metering valve is 1/2". These pipe size are listed
in Table 7.6.3.1..
Bidets
|

Horizontal Spray Bidet
|

Vertical Spray Bidet
|
|
The minimum water pipe size which can supply a bidet
is 1/2".
Bathtubs
|

Soaker Tub
|

Whirlpool
|

Hydro-Massage Bath
|
Bath Faucets
|

|
7.2.10.6.(1)
Supply and waste fittings shall be
certified to CAN/CSA-B125, Plumbing Fittings.
|
Tub and Shower Faucets
|

|
7.2.10.7.
-
Except as provided for in Sentence (2),
all showers valves shall be pressure balanced or thermostatic
mixing valves conforming to CAN/CSA-B125, "Plumbing
Fittings".
-
Pressure balanced or thermostatic mixing
valves shall not be required for showers where the hot water
supply for such showers is controlled by a master
thermostatic mixing valve
|

|
|
conforming to CAN/CSA-B125, "Plumbing
Fittings",
-
Pressure balanced or thermostatic mixing
valves shall be
-
designed such that the outlet temperature
does not exceed 49o
C (120o F).
-
equipped with high-limit stop which shall
be adjusted to a maximum hot water setting of
49oC
(120o F).
The minimum pipe size required to supply a
bath tub or a single head shower is 1/2".
The minimum fixture outlet pipe size for a
bath is 1/2" (Table 7.4.9.3.)
|
Showers
There are two basic designs of showers:
|

Built in Place Shower
May be installed with a manufactured
shower base or a shower base built on-site.
|

Manufactured Shower
|

Manufactured Shower Base
|
7.2.2.3.(1)
Every shower receptor shall be constructed and
arranged so that water cannot leak through the walls
or floor.
|
|
|

Shower Pan Liner
|
If a shower base is built on-site, a shower
pan liner must be installed in order to prevent any possible
leaks through the walls or floor.
7.4.3.1.(1)
Sanitary units, bathtubs and shower baths
shall not be installed adjacent to wall and floor surfaces that
are previous to water.

|
Shower Drains
|

|
7.2.10.6.(1)
Supply and waste fittings shall be certified to CAN/CSA-B125,
"Plumbing Fixtures".
The minimum size of a shower drain serving one shower head is
1/2". Table 7.4.9.3..
In larger public shower type installations a 2" shower drain is
required to drain 2 or 3 shower heads and a 3" drain is
required to drain 4 to 6 shower heads.
|

|
Shower Heads
|

|
7.2.2.3.
- Not more than 6 shower heads shall be served by a
single shower drain.
- Where two or more shower heads are served by a
shower drain, the floor shall be sloped and the drain located
so that water from one head cannot flow over the area that
serves another head.
- Except for column showers, when a battery of
shower heads is installed, the horizontal distance between two
adjacent shower heads shall be at least 750 mm.
|

|
Shower Faucets
|

Shower Faucet
|
Requirements for shower faucets are the same as for the
combination of tub and
shower ones. Amount of water delivered to a shower faucet is
regulated by section 7.6.4.1.
- The flow rates of fittings that supply water to
fixtures shall not exceed the maximum flow rates at the test
pressures listed for that fitting in Table 7.6.4.1.
- Sentence (1) does not apply to a fixture located
in
|

Column Shower
|
|
a heritage building.
In Table 7.6.4.1. shower heads are
limited to 9.50 litres per minute flow at 550 kPa.
The minimum water pipe size required to supply a single head
shower is 1/2". Table 7.6.3.1..
|
7.6.5.2.
-
Except as provided in Sentence (2), all shower
valves shall be pressure-balanced or thermostatic-mixing valves,
conforming to CAN/CSA-B125, Plumbing Fittings".
-
No pressure-balanced or thermostatic mixing valve
is required for a shower if the hot water supply for the shower is
controlled by a master thermostatic-mixing valve conforming to
CAN/CSA-B125, "Plumbing Fittings".
-
Pressure-balanced or thermostatic-mixing valves
shall be
-
designed so that the outlet temperature does not
exceed 49oC
(120oF),or
-
equipped with high-limit stops and adjusted to
maximum hot water setting of 49oC (120oF).
|
 
|

|
|
Thermostatic-mixing Valve
|
Pressure-balanced Valve
|
7.6.5.3.
-
A water distribution system supplying hot water to
any bathtub, shower or hand basin that is accessible to a patient or
resident in a Group B, Division 2 or 3 occupancy or a resident of a
group home, home for special care or residence for
developmentally-handicapped adults shall have one or more temperature
gauges and control devices that are
-
accessible only to supervisory staff, and
-
capable of being adjusted to ensure that the
temperature of the water supplied to the fixture does not exceed
49oC
(120oF).
Lavatories
|

Vanity Lavatory
|

Wall Hung Lavatory
|

Pedestal Lavatory
|
Lavatory Faucets
|

The openings on a lavatory consist of
three holes placed at 4" center to center opening. This design
allows the installation of a standard lavatory faucet with a
mechanical waste assembly.
|
|

An alternative option is to order an 8"
center to center openings. This design allows the installation
of an 8" lavatory faucet with a separate hot and cold control
and a separate spout.
|
|

A third option is a single opening to
allow the installation of either a single lever lavatory with
no deck, or tempered water faucet.
|
7.6.4.1(1)
There are limitations to the volume of water a
lavatory faucet may deliver. Part 7 sets this limit at 8.35 litres per
minute at 413 kPa. Table
7.6.4.1..
The minimum water pipe size to supply a lavatory is
3/8". Table 7.6.3.1..
7.2.2.5.(1)
A lavatory that does not have an overflow shall not
be equipped with a center outlet waste fitting.
7.3.4.1.(3) (about wall
mounted lavatories):
Every wall mounted fixture shall be supported so that
no strain is transmitted to the piping.
The size of the lavatory outlet pipe is 1
1/4".
Kitchen Sinks
|

|
7.2.2.4.(1)
A dishwashing sink and a food preparation
sink shall not have a concealed overflow.
The minimum water pipe size to supply a
domestic or commercial sink is 1/2". Table 7.6.3.1..
Where a faucet to the water distribution
piping is connected by the use of 3/8" flexible tubing, the
maximum length the tubing is 355 mm.
7.6.4.1.(1)
|
|
A kitchen sink is limited to delivering
8.38 litres per minute at 413 kPa.
Table 7.4.9.3.
The fixture outlet pipe size for a single
and a double compartment bowl is 1 1/2".
7.4.9.3.(2)
The part of the fixture outlet pipe that is
common to 3 compartments of a sink shall be one size larger
than the largest fixture outlet pipe of the compartments that
it serves.
|
Service Sinks
|

Wall Hung
|

Floor Mounted
|

Service Sink Faucet
|
The minimum water pipe size to supply a service sink
is 1/2".
Drain sizing for a service sink is determined by the
type of service sink installed:
-
a P-trap sink requires a 2" connection,
-
a S-trap sink needs a 3" drainage
connection,
-
a floor mounted sink will need either a 2" or 3"
connection.
Drinking Fountains
|

|
7.2.10.9.
-
the orifice of every drinking fountain
bubbler shall
-
be of the shielded type, and
-
direct the water upward to an angle of
approximately 45o.
The minimum water pipe size supplying water
to a drinking fountain is 1/2".
The fixture outlet drain pipe size for
drinking fountain is 1 1/4".
|
|